Error codes of the most common gas boilers and their meaning


What to do if the boiler shows F?

This section lists all possible fault codes along with the corresponding corrective actions that the USER CAN perform to restore the equipment to operation (Corrective Action: ...). Other faults MUST only be repaired by a qualified technician.

Error messages are shown on the display in the place where the pressure value in the heating system is normally displayed. Along with the fault code, the telephone icon and the letter F with the corresponding error code flash on the display.

Under normal operating conditions, the 10 most recent error messages can be displayed on the display by pressing both buttons for setting the heating temperature at the same time for approximately 7 seconds.

Code Description
F0 NTC flow temperature sensor circuit open
F1 Return Temperature NTC Sensor Circuit Open
F2 DHW temperature sensor NTC circuit is open
F3 DHW tank sensor NTC circuit is open
F4 Manifold Sensor NTC Circuit Open
F5 Exhaust gas sensor circuit is open
F6 Traction sensor circuit is open
F7 Faulty connection of the NTC temperature sensor in the return line coming from the solar collector
F8 The NTC circuit of the DHW boiler ground sensor is open
F9 Hood Sensor NTC Circuit Open
F10 Short circuit NTC flow temperature sensor
F11 Short circuit NTC return temperature sensor
F12 Short circuit of NTC DHW boiler sensor Short circuit of NTC DHW temperature sensor
F13 Short circuit of NTC DHW boiler sensor
F14 Collector NTC sensor short circuit
F15 Exhaust gas sensor short circuit
F16 Draft sensor short circuit
F17 Short circuit NTC return temperature sensor from solar collector
F18 Short circuit NTC DHW boiler ground sensor
F19 Short circuit of NTC hood sensor
F20 The safety temperature limiter has tripped
F21 The boiler is blocked due to exceeding the threshold value
F22 The water level in the boiler is insufficient, the pump is blocked or faulty
F23 Low water level: large temperature difference between NTC sensors on flow and return lines
F24 Low water level: rapid rise in temperature
F25 Protection against leakage of combustion products into the room has activated
F26 Incorrect current value of the gas valve stepper motor windings
F27 The ionization device signals the presence of a flame, although the gas valve is closed
F28 Unsuccessful first attempt at ignition
F29 Loss of flame during burner operation
F30 Interlock sensor circuit open
F31 Blocking sensor short circuit
F32 Fan anti-freeze protection activated: fan speed is outside the permissible limits
F33 Fan anti-freeze protection activated: pressure sensor open Pressure sensor not open (when fan is not running)
F35 Error in the smoke removal system
F36 Draft diagnostics (only for models with exhaust of combustion products into the chimney)
F37 The fan speed during operation is outside the permissible limits
F38 The measured frequency exceeds the permissible limits
F39 Error in boiler autodiagnostics
F41 Incorrect gas regulation
F42 Coding resistor problem
F43 Incorrect boiler model identification
F49 eBus voltage low
F55 CO sensor error
F58 No feedback regarding preheat
F60 Error in gas valve control +
F61 Error in gas valve control -
F62 Gas valve disabled error
F63 EEPROM error
F64 AOC error
F65 Electronics overheating
F66 IIC data bus error
F67 Flame signal from ASIC is not reliable Diagnosed flame signal input is out of range (O or 5V)
F70 Incorrect OSN
F71 Hot water flow sensor is constantly open
F72 Constant difference in readings of the flow sensor and NTC return temperature sensor
F73 The pressure sensor is not connected or there is a short circuit in it
F74 Malfunction in the electrical part of the pressure sensor (or damaged wire)
F75 Repeated pressure sensor error. After starting the pump, no pressure surge was detected.
F76 Malfunction of the thermal fuse on the primary heat exchanger
F80 Input sensor SHE error
F81 Circulation pump error
F82 Faulty anode tester
F90 Not connected to APC module
F91 Sensor failure in APC module

How to eliminate the error code F28 on the Proterm boiler?

___________________________________________________________________________

The Proterm Panther boiler turned off spontaneously, the screen displays an error code F28. I cleaned the burner and rebooted the unit, but the result was zero. The boiler starts after zeroing, the burner starts working and goes out. Then the ignition cycle is performed again and an error appears. What's wrong? Gas valve is broken. If damage is detected, replace the gas valve. The ignition electrode is unstable or faulty. Diagnose it for the presence of carbon deposits. Adjust the distance between the gas burner and the flame control electrode if necessary. Inoperability of the gas device. Inspect the coils in the gas valve to determine a possible open or short circuit. If these problems occur, replace the gas valve.

The gas valve becomes stuck. Attach a silicone hose to the fitting located on the front of the valve and apply increased pressure. There is not enough power to ignite. Adjust the ignition power when using the service menu. Malfunction or defect of the control board. The ignition transformer stopped working. Reboot the device. If the error occurs again, the electronic board must be replaced.

Grounding should be checked. The sheathing should not have tension. Excessive moisture can cause the device to block. It is necessary to clean the furnace, ionization electrode and gas burner unit from condensation. Failure of the flame control electrode functions. The control board has detected a flame, although no combustion occurs. Inspect the electrical wiring of the flame control electrode. Poor contacts and breaks are likely. The electrical circuit from the ionization electrode to the control board is inspected for the possibility of a short circuit. The ionization electrode may touch the burner assembly. Damage to the electronics board. It needs to be changed.

___________________________________________________________________________

Similar questions

  • How to reset error code A5 on a gas boiler Arderia
  • How to eliminate error code 108 for an Ariston gas boiler
  • How can you reset the E10 error code on a Baxi boiler?
  • Why can a Beretta gas boiler heat up and make a loud noise?
  • Why does a Bosch gas boiler reduce pressure?
  • For what reason does the Buderus boiler not operate in hot water supply mode?
  • Why does the pressure drop in the Celtic gas boiler?
  • Why did the Daewoo double-circuit boiler begin to hum and heat up?
  • How to eliminate error E4 on an Electrolux boiler
  • Why does a Ferroli gas boiler not work on hot water supply?
  • Why does the Immergas boiler constantly turn on and off when heating
  • Why did the Junkers wall-mounted gas boiler start to hum and get warm?
  • Why does the Navien boiler give error 10, how to fix it
  • Why does the Neva Lux gas boiler display error 03, how to fix it
  • How to eliminate error F22 on a Proterm gas boiler
  • Why does the Rinnai boiler not function on hot water supply?
  • Why does the Vailant gas boiler show error F36, how to fix it
  • For what reasons does the Visman gas boiler show error code F4?
  • The pressure of the Electrolux gas boiler decreases, what is the problem?
  • What is the problem if the Ferroli gas boiler shows error code F05, how to fix it
  • Why did the Arderia boiler start giving error E2, how to fix it
  • For what reason did the Ariston gas boiler constantly start turning on and off in heating mode?
  • For what reason does the Baxi gas boiler not hold pressure?
  • Why did the Bosch gas boiler start to issue error code C6, how to fix it
  • The pressure of the Buderus boiler decreases, what is the problem?

___________________________________________________________________________

___________________________________________________________________________

  • Why did the Arderia boiler often turn on and off when heated?
  • What is the problem if the Ariston gas boiler shows error 607, how to reset it
  • How to eliminate error code F28 on the Vailant boiler
  • Why does the Visman boiler not function for hot water supply?
  • How to eliminate error 43 on a Rinnai boiler
  • This is why the Neva Lux boiler began to heat up and hum loudly
  • Why does the Proterm boiler not work on hot water supply?
  • How to eliminate error 01 on an Immergaz gas boiler
  • For what reason does the Navien boiler not work in hot water supply mode?
  • How to eliminate error E1 on an Electrolux boiler
  • How to eliminate error code F37 on a Ferroli boiler
  • How can you eliminate error 6A on a Buderus gas boiler?
  • Why did the Daewoo gas boiler stop holding pressure?
  • Why does a Bosch gas boiler not operate on hot water supply?
  • What is wrong with the Baksi boiler if it gives error E01
  • Beretta gas boiler does not hold pressure, what is the reason
  • What is wrong with the Arderia gas boiler if it starts giving error A6
  • The pressure in the Ariston gas boiler decreases, what are the reasons?
  • For what reasons can the Rinnai boiler heat up and hum?
  • Why did the Visman boiler constantly turn on and off when heating up?
  • Why does the Arderia boiler not operate in DHW mode?
  • For what reasons did the Ariston wall-mounted boiler begin to display error code 501?
  • What is the problem if the Baksi boiler gives error E03, and how to fix it
  • Why does the Buderus boiler give error 3C, how to reset it
  • Why does the Proterm boiler often turn off and turn on when heating?
  • What is wrong with the Ariston boiler if it shows error 607
  • How can I eliminate error code 10 on a Navien boiler?
  • What is the problem with the Electrolux boiler if it displays error code E3
  • How to eliminate error F36 on a Vailant gas boiler
  • What is the problem with the Proterm gas boiler if it gives error F25
  • How to eliminate error code F5 on a Visman gas boiler
  • What is the problem with the Ferroli boiler if it shows error code F05
  • How to eliminate error E03 on a Baxi boiler
  • What is wrong with a Bosch boiler if it shows error C6
  • What is the problem with the Buderus gas boiler if it displays error code 3C
  • What is the problem if the Rinnai boiler gives error 99, and how to fix it
  • Why does the Beretta boiler display error A03, how to fix it
  • Why does the Junkers boiler constantly turn off and on in heating mode?
  • Why does the Daewoo boiler constantly turn off and turn on when heating?
  • Why does a Bosch boiler constantly turn on and off when heating?
  • Because of what the Thermon boiler often turns off and turns on when heating
  • Why does the Celtic boiler constantly turn on and off when heating?
  • What is wrong with the Westen gas boiler if it displays error E01
  • How to eliminate error code A01 on a Corestar gas boiler
  • How to eliminate error code F1 on a Senor Duval gas boiler
  • How to eliminate error code A6 on a Celtic gas boiler
  • What is wrong with the Elsotherm boiler if it starts giving error E1
  • For what reasons did the Bugatti gas boiler begin to display error E01?
  • How can you eliminate an error with code E2 on a Motan boiler?
  • Why does the Immergaz boiler lose pressure?
  • Why did the Kiturami gas boiler stop holding pressure?
  • The pressure drops in the Korea Star gas boiler, what are the reasons?
  • Why doesn't Mora's boiler hold pressure?
  • The pressure in the Navien boiler is decreasing, what is the problem?
  • The pressure in the Proterm gas boiler decreases, what are the reasons?
  • Why does the Rinnai boiler not hold pressure?
  • For what reasons does the Ariston boiler display error code 101?
  • How to eliminate error F20 on the Proterm boiler
  • For what reasons does a Daewoo gas boiler show an error with code E3?
  • How to eliminate error code 16 on a Navien boiler
  • For what reasons does the Electrolux boiler display error E2?
  • How to eliminate error F20 on a Vailant gas boiler
  • What is the problem with the Beretta boiler if it starts giving error A02
  • How to eliminate error F2 on a Visman boiler
  • For what reasons does the Neva Lux boiler show error code 02
  • How can you eliminate error A03 on a Ferroli boiler?
  • For what reasons does the Baxi gas boiler show error E02?
  • How can you eliminate error E9 on a Bosch gas boiler?
  • For what reasons does the Buderus gas boiler give error 2E?
  • How to eliminate the E3 error on the Oasis boiler
  • For what reasons does the Rinnai boiler show error 16?

___________________________________________________________________________

___________________________________________________________________________

  • Heating boiler piping
  • STS boilers
  • KVT boilers for solid fuel
  • Pellet boiler Peresvet
  • Steel floor standing boiler Raton
  • Solid fuel boiler Thermology
  • Errors and malfunctions of the Termet gas boiler
  • Termona boiler repair
  • Boiler repair Nova
  • Hermann boiler service
  • Comparison of gas boilers Lemax Premium-20 and Danko-20s

___________________________________________________________________________

  • Daewoo boiler maintenance
  • Demrad boiler malfunctions
  • Mora boiler malfunctions
  • Westen boiler repair
  • Malfunctions of Immergaz boilers
  • Types of solid fuel boilers
  • Models and design of combination boilers
  • Liquid fuel and double-circuit boilers
  • Cast iron boilers on coal
  • Boilers with modeling burners
  • Imported boilers for heating systems
Rating
( 1 rating, average 4 out of 5 )
Did you like the article? Share with friends:
Для любых предложений по сайту: [email protected]