Refusal to use centralized heating and water supply lines, the creation of autonomous heating systems and hot water supply at home is becoming commonplace.
This is convenient for owners of private houses or apartments; it allows them to independently make decisions about the beginning and end of the heating season or home heating modes.
Retail chains offer a wide range of gas boilers, on the basis of which the most efficient and economical heating systems are created.
European companies are considered confident leaders in the production of heating equipment, but their colleagues from Southeast Asia have achieved considerable success.
Let's consider the brightest representatives of heating equipment from South Korea - Arderia gas boilers.
Main types
The Arderia brand is owned by the South Korean company Daesung . The products of this company are widely known in the world and are in high demand. The main feature of the company is its approach to the production of heating equipment.
Most work operations are performed by automated lines, which eliminates miscalculations or negligence. The Arderia brand was created to place gas boilers on the Russian market, which were produced in the following types:
By installation type:
- wall- mounted Designed for hanging installation indoors (usually in kitchens).
Floor-standing models are not produced, as they require a separate room and are in less demand.
By feature set:
- single-circuit . Designed only to supply the heating system with hot coolant at a given temperature;
- double-circuit . The units are prepared for simultaneous heating of the coolant and supply of hot water;
The following types of heat exchanger are available::
- with separate heat exchanger . These are boilers in which the primary unit consists of pure copper (99%), demonstrating high resistance to temperature changes and the absence of corrosive processes. The secondary heat exchanger is made of stainless steel, has high heat transfer capacity and shows remarkable performance;
- with bithermal (combined) heat exchanger . This is a “pipe-in-pipe” design. The coolant and water for the hot water supply line simultaneously pass through it without mixing with each other. This design allows you to significantly increase and stabilize the hot water supply at home, but requires taking all possible measures to protect against scale. The complex cross-section of the heat exchanger pipe is very difficult to clean, and replacing a defective unit is too expensive and is not carried out everywhere.
NOTE!
The design of the boilers meets modern requirements for the functionality and efficiency of heating technology. The units have all the necessary certificates and can be used in residential and public premises.
Series and models
Arderia gas boilers are available in the following series:
Series "B"
“B” series units are manufactured in Russia, at Daesung’s own production facilities . The model range consists of dual-circuit units with a bithermic heat exchanger made of copper.
The power of the models ranges from 10 to 24 kW, which is suitable for heating rooms from 53 to 250 sq.m.
Main parameters of the models:
- modulating burner;
- ability to work with low inlet gas pressure (up to 4 bar);
- silent circulation pump with a “wet” type rotor;
- there is a self-diagnosis and flame detection system;
- availability of frost protection;
- The units have been adapted to Russian climatic and technological conditions.
Gas boilers of the “B” series are reliable and economical . Each unit undergoes a separate quality control inspection. There is multi-stage protection against operational overloads or freezing.
Series "D"
A series of gas double-circuit boilers with a power of 10-24 kW, capable of heating rooms from 53 to 250 sq.m. Equipped with two heat exchangers .
Primary (main) copper, secondary (for hot water supply) - stainless steel. Parts and materials from the best European manufacturers, as well as the company’s own developments, were used in production.
Specific features of the units:
- possibility of conversion to liquefied gas;
- the gas valve is adjusted via the control panel;
- two options for installing a chimney - separate or coaxial;
- possibility of remote control via an application on a smartphone;
- There are contacts for connecting a room sensor.
The design of boilers in this series is practically no different from the design of the best European models . At the same time, the prices of Arderia boilers are at least two times lower than those of analogues from European countries.
This increases the demand for Korean units and increases their importance in the eyes of buyers.
ESR 13-20 kW
The power of boilers of this series is in the range of 16-18.6 kW . It includes two models - ESR 2.13 and ESR 2.20. In terms of their set of functions, they are dual-circuit units with a closed combustion chamber. Designed for heating rooms from 65 to 200 sq.m.
Manufactured in South Korea, at our own production facilities.
Capabilities of boilers of the ESR series 13-20 kW:
- it is possible to connect to gas lines with low pressure (up to 5 mbar);
- adjustable turbocharging;
- a circulation pump with a “dry rotor” was used, allowing maintenance without draining the coolant from the system;
- a control panel is used that operates at a distance of up to 40 m;
- there is a self-diagnosis system;
- built-in voltage stabilizer that corrects differences from 156 to 280 V.
Units of the ESR 13-20 kW series are adapted for operation in Russian conditions . They are equipped with frost protection
ESR 25-35 kW
This model line includes the ESR 2.25, ESR 2.30 and ESR 2.35 units. Power range - from 12.2 to 40.7 kW . Capable of heating areas from 122 to 407 sq.m.
Equipped with copper primary and stainless steel secondary heat exchangers, a closed combustion chamber, modulated burner.
Main settings:
- electronic flame ignition system;
- the possibility of converting gas equipment to consume liquefied gas;
- automatic maintenance of coolant and hot water heating mode;
- the presence of an ionization sensor that monitors the presence of a flame;
- adaptation of the boiler to Russian conditions.
The units demonstrate reliability, stable operation, and are easy to control and adjust . Combined with low prices, these qualities make them competitive in the market of heating devices.
Arderia Boiler Operating Manual
7 Jun
g. — Pros and cons of reliable Arderia ESR series models. Gas boilers are designed for heating and hot water supply. Operating a boiler with faulty components such as Arderia may result in damage to the boiler and pipes as a result... When installing the boiler, comply with the requirements of this manual and regulatory documents. Gas boilers Arderia - Operation and repair. Tell me, is it possible to reduce the power on the arderia esr ffcd wall-mounted boiler? Program parameter P5. We did.. Description of error codes for Arderia B10, B14, B boilers. Operating a boiler with faulty elements such as Arderia can lead to damage to the boiler and pipes as a result of.. When installing the boiler, follow the requirements of this manual and regulatory documents. 13 Mar g. — Instructions and guidelines for installation and use of Arderia gas boilers Boiler diagram Purpose of board switches. 26 Nov - Arderia boilers of the ESR series are designed for heating and hot water supply. Reliable primary heat exchanger.
I will look for where the CO is leaking to minimize the recharge. An Arderia wall-mounted boiler was installed, which worked without problems for 1 year. Suddenly at night there was a loud noise from the pump, and in the end it gave an A4 error. It is clear that the pump starts up at the beginning, and then stops and gives an error. 2 gas workers came and said that the pump was a waste pump and you had to buy either a new one of the same type, or install a regular one into the system.
I was only confused that sometimes the pump did start working, namely when water was added to the system. Not believing the gas workers, I removed the pump, disassembled it, cleaned it on all sides, put it back and everything works. Only sometimes this loud noise still appears from the pump, as if something is striking, but I don’t understand where, or the bearing has fallen apart, maybe someone has encountered this?
When the gas boiler Arderia 2 was operating. I reduced this parameter from tee to tee degrees. The boiler rarely turns on until the batteries have completely cooled down. I may be saving gas, but the feeling of comfort is gone.
Arderia boiler instructions
While I was adjusting the temperature of the carrier, the batteries were always warm, but now, it feels like this is the degree to which the temperature drops before turning on the device. And the temperature sensor in the remote control is lying by 5 degrees.
It’s not something you changed, most likely, I’ll be at home, I’ll definitely see how it’s marked. In general, there is no particular point in reducing the temperature, only if there is a risk of burns, for better coordination with a heated floor without a mixing unit. To reduce the formation of hydrogen. If radiator heating and the number of sections is not enough, or the boiler power is at its limit, and you reduce it to 60, in the coldest days it may not heat the air to the required temperature.
The air thermostat mode is much more convenient, set the air temperature and it holds, and the coolant thermostat will need to be constantly adjusted “more or less” as in the operating manual for the Arderia boiler. The only problem is choosing where to install the remote control; the unit will be guided by the temperature of this particular room. If you opened it to ventilate a room with a remote control, the boiler will add power to compensate, while other rooms, if isolated, with a door will begin to overheat a little.
You can put the remote control in the coldest room, and in others put thermostatic heads with taps. When the boiler switches to hot water supply, should it immediately operate at maximum power, the Arderia boiler operating manual, after a couple of seconds, reduce the power to the set one. Or is this a glitch? A couple of days ago it began to hum strongly at maximum power, it seems that when starting the hot water supply, at first there is too much gas pressure, and after a few seconds it decreases.
Malfunction of the Arderia ESR 2 boiler. When operating from a room thermostat, the following occurs: The coolant temperature is set. The air temperature does not change.
I am concerned about 2 points: In my opinion, it should rest longer, secondly, on what basis does it turn on if the air temperature in the room does not change? So this is great: In general, with warm floors, the thermal inertia of the house should be quite good.
My room temperature drops by 1 degree. This is according to the room thermometer, and the unit always costs as much as it is set. An Arderia 2 gas boiler is installed. Is it necessary to provide instructions for the evacuation of armed equipment in case of fire in the maximum and minimum gas pressure while programmatically reducing its power to minimum values?
gas boilers arderia boilers
The Arderia 2 double-circuit boiler is in operation. Now the pump makes a loud noise during operation, but the control panel does not display any errors. When disassembling and inspecting the pump, all bearings were intact, and no signs of rubbing were found. Please advise what could be wrong? The noise of the bearings is quite specific, try using a screwdriver to listen to exactly where the noise is in the pump, and then decide what exactly to change.
Tell me, who knows, I’m going to clean the heat exchanger of the Arderia boiler with a booster. Is it possible to do this without removing the heat exchanger, just connect the hoses to the supply and return without disassembling anything? The boiler began to work strangely, you set any temperature, even 60 degrees, 70 or 75, it makes no difference, the room temperature does not rise above 23, the warm water 60 degrees has disappeared altogether, and the hot water 80 degrees floats either hot or cold.
I suspect that your three-way valve is constantly spinning, listen through a 3-way screwdriver with characteristic clicks. A priori, we believe that everything worked for you previously. When scale forms in the secondary heat exchanger, there are few symptoms. It boils, but does not give an error. As a result, it turns on and off constantly. I’ll say right away that everything works, I invited gas workers, they checked all the physical components. Everything is cleaned, the flow of water through the boiler is ideal.
The pump may not be running enough. I tried with Zyrtec drops running for children, instructions to turn off the gas supply valve until the flame reduces. Then it works without turning off. It seems that there is insufficient water circulation. The pump was disassembled, there is no visible damage, the speed is normal, it turns. The coolant flows not only through the boiler, but also through the heating system.
If everything is fine in the heating unit, check it. You can also check the 3-way valve, but it doesn’t seem to be boiling. I set the temperature to 55 and stood at 45 degrees. The needle on the pressure gauge has risen 2 notches. The heating has worked, the arrow has returned to 1. If the three-way valve is leaking, then the operating manual for the Arderia boiler is small.
To tell for sure, you need to turn off the heating. Isn't this very dangerous for the boiler if you keep it under control at all times? Most likely, the pressure in your expansion tank is insufficient or your heating system has a volume of more than liters. Unfortunately, I don’t know what kind of heating system you have; the installers, when putting it into operation, should have configured it so that you would not have questions about non-working devices, in particular the substation.
If the equipment is working, the main thing is not to interfere. Error A2 - The fan is running at low speed. Insufficient speed of the boiler operation manual arderia fan has got foreign objects. Error A3 - The circulation pump is faulty.
The pressure sensor turned on before the pump started. The pressure sensor is clogged with dirt. Error A4 - Overheating sensor triggered. All shut-off valves of the heating system are closed. Heating circuit filter clogged. The 3-way valve is faulty. Damage to the DHW water flow sensor. Error A5 - Low coolant pressure. Small volume of water in the heating system. Presence of air in the heating system.
The circulation pump is functioning, but the speed is insufficient or the impeller is damaged. There is a problem with the pump pressure sensor. Instructions for the machine indesit water in the heating system. Error A6 - Ignition fault. Error A7 - Gas valve is faulty. Gas valve relay closes.
Error A8 - Residual flame. There is a residual flame in the chamber although the gas valve is not energized. The gas valve diaphragm is damaged. Replace the control unit in the Arderia boiler operating manual if replacing the gas does not correct the situation. Reducing the water temperature in the unit to 5 degrees.
Error AA - Boiling. All heating circuits are closed. The heating system filter is clogged. Malfunction of the hot water flow sensor. There is a short circuit in the thermostat. Incorrect connection between thermostat and contacts. Error AE - Chimney blocked. There may be foreign objects in the gas duct.
Make sure the lines are intact. If the error persists when the temperature rises, contact customer service. E1 - Ionization sensor error - lack of expected flame. Displayed when ignition fails, or after an unexpected loss of flame during normal operation of the device.
Check for gas supply. The control system will attempt to restore normal operation for 60 minutes, then lock out. You can remove the lock by pressing the MODE button. If the error is caused by a boiler malfunction, contact customer service.
E2 - Differential air pressure sensor error. Displayed in abnormal draft situation, may also be caused by a malfunction of the fan or air pressure sensor. Within 15 minutes, the control system will try to restore normal operation of the Arderia boiler. Make sure the chimney is in good condition, check if it is blocked. If the error is not resolved after 15 minutes, contact customer service.
E3 - Operating manual for Arderia boiler with overheating safety thermostat. Displayed in situations where there is no coolant or its circulation in the heating circuit, the Arderia boiler operating manual may be caused by a pump malfunction.
Open the hot water tap to lower the temperature, check the condition of the valves and lines of the heating circuit. If the error is caused by a malfunction or breakdown, contact customer service. E5 - BInTem temperature sensor error. Displayed when the cold water temperature sensor BInTem is faulty.
Close all hot water taps for normal operation of the Arderia boiler in heating mode. To troubleshoot the problem, contact customer service. E6 - BOuTem temperature sensor error. Close all hot water taps for normal operation of the boiler in heating mode. E7 - Gastrocalm instructions for use price of WarmTem temperature sensor.
Displayed if the WarmTem heating circuit coolant temperature sensor is faulty. There may be a communication error with the sensor, and when communication is restored, the blocking will be removed automatically.
E8 - Ionization sensor error - presence of residual flame. Displayed in a situation where there is a residual flame, as well as as a result of an error in polling the ionization sensor.
Remove the lock by pressing the MODE button. The repeated occurrence of error E8 means a malfunction of the unit. In this case, you should immediately shut off the gas supply to the boiler. E9 - Coolant pressure sensor error. Displayed in a situation of low pressure or lack of coolant in the heating circuit.
Check for leaks from the heating circuit and coolant pressure. Once the cause of the malfunction is eliminated, the blocking will be removed automatically. If the error is caused by a malfunction, call a professional. With open and closed combustion chamber. Methods of repair and service, adjustment of operating parameters. Maintenance recommendations.
Read more Gas heating boilers Vaillant Models: Service, maintenance, settings of functional components.
Recommendations for repair, maintenance and service. Elimination of errors and malfunctions. Setting and adjustment methods.
Installation, assembly and connection. Settings of operating modes and additional equipment. Malfunctions and error codes. Adjustment of gas automatic equipment Eurosit Replacement of thermocouple and maintenance of pilot burner. Recommendations for eliminating errors and malfunctions. Settings and adjustment of operating modes. Repairs, adjustments and malfunctions. Settings for functions and modes. Working with Xital remote control. Adjustment of work by temperature and pressure.
Operation with Logomatic control system and indirect heating boiler. Components and operating functions. Maintenance and prevention. Recommendations for setting operating parameters. Lemax - repair and adjustment Models of gas floor-standing boilers Premium, Leader, Patriot. Adjustment of automation Eurosit, Minisit, Sit Nova. Operation and service. Recommendations for adjustments in the operating manual for the Arderia boiler modes. Wall and floor models. Operating functions and setting up service modes.
Installation of an automatic pellet burner APG, 36, Troubleshooting tips. Operating modes and setting up service parameters. Heating boilers Alfaterm Description of floor-standing boilers of the Beta model and wall-mounted gas boilers Sigma. To clean the smoke pressure sensor, it is necessary to disconnect the wiring from it, dismantle the device and carry out inspection and cleaning. To replace the circulation pump, you need to drain the water from the system, disconnect the pump from the wiring, unscrew the pipes, and then install a new element.
If the filters become clogged, they are removed and cleaned or replaced. Repair of the electronic unit phytolax tablets instructions for use reviews price entrust to professionals. In addition to this information, we have already covered all the nuances of operating such popular boiler equipment for private homes.
We hope that the information provided will make it easier to purchase or use such a boiler. E-mail is not necessarily published. Providing a full range of services for the selection and configuration of household equipment for heating systems.
List of all boilers instructions. Guarantee for all 5 years! Operating manual for the Arderiya boiler; review of two models. Advantages of the models; operating instructions; Comparative table and typical faults. This brand is produced in South Korea under license from Daewoo. The Arderia model range is represented by the following family: The use of copper as the material of the primary heat exchanger, and stainless steel as the material of the secondary heat exchanger, increases the efficiency and durability of the equipment.
The function of monitoring the electrical voltage supplied to the boiler helps to avoid failure of the control board due to voltage surges. There is no need to use an additional voltage stabilizer. The fan for forced smoke extraction operates on direct current, which increases its service life because the speed of the blades is optimized. Improved operating conditions for the circulation pump. A substantive review of two models So, we will analyze two popular modifications from the above series, and also provide operating instructions for these gas boilers. Operating instructions for the Arderia boiler.
The markings of the models taken as an example are as follows: Advantages of the models instruction manual The main advantages of these boilers satisfy the most demanding consumers. The boilers have protection against overheating; if the heat exchangers overheat, the gas burner turns off. There is a built-in instruction manual for downloading torrent stabilization.
They can operate on both natural and liquefied gas. First of all, the required temperature is adjusted using the control panel. Thanks to the temperature sensor, the heat generator is turned on, the temperature rises to the set parameter inside the room. When the required temperature in the room is reached, a special sensor turns off the gas burner. As the temperature drops, the cycle repeats. To set the hot water supply, the temperature is also set using the control panel.
After warming up the hot water supply circuit, the water temperature is maintained at a constant level. Comparative table and typical malfunctions Now let’s summarize the data directly for each modification into a table, where we will also indicate the average cost of the equipment.
There are problems with sensors and with the pump. If the smoke pressure sensor is clogged, it may turn off; it is easy to clean it yourself. If the circulation pump breaks down, the overheating sensor is triggered; the Arderia boiler operating manual turns off; the boiler is switched off; it is better to replace the pump completely. Operating manual for the Arderia boiler, jumps in the operating temperatures of the coolant mean, in addition to possible breakdown of the pump, probable clogging of the water filters.
Gas boilers Arderia - Operation and repair | Make sure that the supply flange of the chimney pipe, intended for connecting the corrugated pipe from the device, is directed upwards. |
Arderia boiler instructions download in pdf | Please advise what could be wrong? |
Bepanten plus instructions for use analogues | When installing the Arderia boiler Arderia esr 2. |
Codelac Broncho instructions price Minsk | All functions of monitoring and controlling the operation of the unit are implemented using a remote control panel. |
Gas boilers Arderia: operating instructions, how to troubleshoot - construction | Operation with Logomatic control system and indirect heating boiler. |
Positive design features
It should not fall under its own weight.
Errors in Vailant gas boilers. Thanks to this, the unit can operate in the range from to V. Connecting and commissioning the Buderus Logomax U boiler This design of the unit reduces its sensitivity to the conditions of coolant flow in the pipelines, since various deposits inevitably form there over time, impairing the lubrication of rotating parts. The boiler is equipped with a DC fan that can operate at any required speed. Related resources:
imperial-perm.ru
Specifications
Let's look at the parameters of Arderia gas boilers:
Characteristics | Values | |||
Arderia D10 | ESR 2.20 | ARDERIA ESR 2.35 | ||
Boiler type | Gas heating | |||
Fuel type | Natural or liquefied gas | Natural or liquefied gas | ||
Installation method | Wall | |||
Thermal power | 10.9 kW | 8.6-23.3 kW | 12.2-40.7 kW | |
Gas consumption (max) | 1.2 m3/h | 2.73 m3/h | 4.49 m3/h | |
Power supply | 220 V 50 Hz | |||
Dimensions | 410x652x243 mm | 420x660x200 mm | 460x700x205 mm | |
Weight | 26.2 kg | 24 kg | 26 kg |
General – Gas Boiler Arderia Instructions
Contained in the “Operating Instructions” section. ARDERIA boilers are gas wall-mounted automatic boilers with a combustion chamber. The temperature in the heating circuit is in the range of 40. When pressed a second time, the boiler switches to the “SUMMER” mode in which the boiler operates.
Problems with gas boilers. Or installing a stabilizer at reduced voltage.
Problem 2: Water boils in the heat exchanger when operating on CO. Solution: Clean the filter on the return line, the pump is faulty, the pump is clogged, the 3-way valve is faulty.
The gas wall-mounted boiler Arderia esr 2.13 ffcd has a reliable protection system, which includes protection against overheating, protection against freezing, protection against voltage surges and protection against gas leaks.
Washing the arderia boiler. Descaling a double-circuit gas boiler Proskurov - Duration: 1:48. The Arderia boiler of the ESR-2.xx series is designed for heating and hot water supply. The boiler is a wall-mounted gas boiler with a closed combustion chamber, a built-in gas burner with proportionally controlled (modulated) gas supply.
The temperature in the heating circuit is in the range of 40. When pressed a second time, the boiler goes into the “SUMMER” mode in which the boiler operates. Gas boilers and burners are created. Arderia ESR 2.13 16 kW. The instructions with it are bare, like a Chinese speaker. Contained in the “Operating Instructions” section.
Topic in the Gas boilers and burners section, created by Arderia ESR 2.13 16 kW. The instructions with it are bare, like a Chinese speaker. Question: We installed and connected a gas wall-mounted boiler Arderia 2.13, which served without complaints for exactly 2 years and malfunctions began. I read the instructions, I am inclined to think that it is necessary to flush the DHW heat exchanger. So that consumers can expand their knowledge about boiler equipment, let's talk about one of the popular models - consider the Arderia gas boiler, instructions for it, approximate prices. For safety, please read the instructions carefully.
Problem 3: The boiler works almost constantly, the gas consumption is huge, the temperature does not rise. Reason: cement heat exchanger clogged with dust.
The next room was undergoing renovations, the floors were being poured, and the boiler was pumping out all sorts of rubbish. Problem 4: Flame separation during boiler operation, the boiler stops, the ionization electrode does not see the flame. The reason is icing of the inlet channel of the coaxial pipe. The way out of the situation is that in the turbines, on the sides of the outlet pipe there are two holes closed with plugs.
The operating instructions for Vailant gas boilers will help you first. Methods for troubleshooting gas boilers Arderia ferroli-02. Instructions and guidelines for installation and use of Arderia gas boilers Boiler diagram Purpose of control board switches Values of control board parameters Adjusting gas pressure Setting maximum power mode Connection. Before purchasing a gas boiler of the Arderia brand, you should carefully study the operating instructions. It is also important to be aware of the possible ones. Help in choosing a gas wall-mounted boiler Arderia (Arderia). The South Korean-made Arderia gas boiler is far from the best. The instructions will help you understand each function in more detail.
Arderia double-circuit gas boilers made in South Korea (Daesung) are manufactured under license from a well-known company. This must be taken into account when purchasing, since for Arderia gas boilers even this feature is noted in the instructions. Washing the arderia boiler. Vitaly Matveev Descaling a double-circuit gas boiler Proskurov - Duration: 1:48. Before purchasing a gas boiler of the Arderia brand, you should carefully study the operating instructions. It is also important to know about the possible ones. Manufacturer: ARDERIA LLC, 140014 Moscow region, Lyubertsy district, Lyubertsy city, Electrification street, building 7A. PURPOSE The wall-mounted gas heating boiler ARDERIA series S, B, D (hereinafter referred to as the boiler) is designed to operate as a... Problem 1: The boiler lights up and goes out, causing an emergency Error. The Arderia boiler (ARDERIA) is weird. Boiler ESR 2.25 FFCD with a separate chimney, in operation for 3 months in a new house, network gas, normal gas pressure, actual supply voltage 220, air supply from the street through a pipe 80 length 200, clean air.
USER'S MANUAL. Leave the shut-off valves of the heating system and the gas tap open even if you do not use the Arderia boiler for a long time in winter. Problem 1: The boiler lights up and goes out, causing an emergency Error (open the instructions and find its location).
Gas wall-mounted boiler Arderia B16 buy in Nizhny Novgorod price. The page contains: instructions, photos, descriptions, reviews and technical information.
Take a screwdriver, unscrew the screw and open it slightly. Thus, we provide the combustion air necessary for the boiler from the apartment.
devrusoft.fo.ru
Advantages and disadvantages
Advantages:
- efficiency, a successful set of performance qualities;
- the ability to heat the coolant and supply hot water for domestic needs;
- convenient control, there is a remote control and the possibility of remote influence via the Wi-Fi module;
- the presence of a built-in voltage stabilizer capable of correcting drops of up to 150 V;
- boilers are designed for operation in difficult Russian conditions;
- the self-diagnosis system continuously monitors emerging problems and notifies the owner about them;
- there is multi-stage protection against all overloads, coolant freezing, voltage drop, etc.;
- the price of the units is significantly lower than that of European analogues of the same quality.
Flaws:
- need to connect power supply. If there is a sudden shutdown in winter frosts, there is a risk of being left without heating;
- the company emerged relatively recently and has not yet managed to create an extensive network of service centers;
- The power of the units is limited and does not allow their use in large rooms.
Judging by the relevance and high demand, the shortcomings are not critical and are quite surmountable.
CAREFULLY!
Some users note a high noise level or some time lag when supplying hot water. However, such features are typical for all models of gas boilers from European and Russian manufacturers.
Operating and setting instructions
The initial (basic) setting of gas boilers is carried out at the manufacturer. During installation and first start-up, it is necessary to correct the factory settings in order to combine the existing operating conditions with the needs of the mechanics and electronics of the boiler. These actions must be performed by employees of service centers or warranty workshops.
Independent intervention in the design of gas appliances is prohibited . Operating settings such as adjusting the temperature or turning off the heating for the summer are permissible and must be carried out by the user.
Operation of the units is not difficult . It is necessary to pay attention to the display readings and, if necessary (if an error code appears), call a technician. Clean the housing from dust and dirt, carry out technical inspection and other procedures in a timely manner. Before starting work, you should carefully study the instructions and follow their instructions.
Basic faults
The main malfunctions of Arderia boilers should be considered:
- if the outlet hole becomes icy, the pressure sensor may be turned off and the chimney may be blown out;
- stopping or falling fan speed means the entry of foreign objects or particles into the working space of the impeller;
- the overheating sensor is triggered when the circulation stops (pump failure) or the supply valves are closed;
- the boiler does not light up. This indicates a failure of the gas equipment (valve) or a power outage to the main line.
All problems that arise are immediately detected by the self-diagnosis system . It issues a special code on the remote control, which indicates a standard situation with a malfunction of a particular sensor, component, or part. A complete list of codes is contained in the user manual, which should be kept at hand.
Among them, the most common designations are the following::
Code | Decoding | Causes |
A1 | Air pressure sensor malfunction | Short circuit, icing of the outlet |
A2 | The rotation speed of the fan axis has dropped | Interference, foreign objects or debris on the impeller |
A3 | The pressure sensor triggered before the pump was started | The sensor is clogged with dirt and needs cleaning. |
A4 | Coolant overheat sensor | Circulation stops due to pump or three-way valve failure |
A5 | The coolant pressure has dropped | There is little water, the system is airy, leaks have appeared |
A6 | No ignition or chimney blocked | Gas pressure has dropped, the chimney is clogged with soot or ice |
A7 | Gas valve short circuit | The control unit has failed |
A8 | There is a flame on the burner, although there is no gas supply | Problems with the gas valve, control unit. Check grounding. |
A9 | Coolant frozen | Temperature drop to -5° |
AA | The coolant has boiled | Circulation stopped, valves closed, problems with three-way valve or pump |
AND YOU | Thermostat failure | Breakage, poor contact |
AE | Chimney blocking | Icing, deformation, foreign objects |
Errors in gas boilers Arderia (Arderia) and methods for eliminating them
Any gas boiler needs regular maintenance and preventive measures. It happens that the causes of problems are external factors: low pressure in the line, voltage drops, etc.
We recommend: Leaks in the heating system and plumbing: how to stop and how to repair them
Malfunctions of Arderia gas double-circuit wall-mounted boilers are detected in the form of codes on the screen. Their decoding is available in the operating instructions.
Error code | Cause | How to fix |
A1 | Short circuit of the air pressure sensor (blowing out the chimney). Usually occurs when the smoke exhaust channel is clogged or reverse draft occurs. | You should inspect whether the chimney is clogged with debris or whether ice has formed on it, which is preventing smoke from escaping and air flowing to the burner. Check for the presence of reverse draft; if there is any, the cause of the occurrence should be identified. Perhaps you need to put a deflector on the pipe or change the design of the chimney |
A2 | The fan rotates slowly. Appears due to a malfunction of the element, a break in its wiring | It is necessary to check the operation of the fan, whether anything is interfering with it. If necessary, clean the part from debris. ...Perhaps ice has appeared at the end of the coaxial pipe, preventing smoke from escaping from it |
A3 | Problems with the circulation pump and its sensor Often occurs if the pressure sensor is clogged | You should check the sensor wiring and diagnose the pump. If necessary, clean and connect the wires |
A4 | The overheating sensor has tripped. The reasons are as follows:
All heating system shut-off valves may be closed | Clean filters from clogs. Unblock the circulation pump and clear its visible parts of debris. Open shut-off valves. Check the functionality of the three-way valve and the DHW flow sensor. Replace broken items |
A5 | Low coolant pressure. Possible reasons:
| There may be a leak in the heating system. All radiators and pipes should be checked for its presence. It is necessary to remove air pockets using Mayevsky taps. The speed of the circulation pump impeller should be adjusted. Replace faulty elements |
A6 | There is no ignition. The smoke exhaust pipe is blocked. Usually the reasons are:
| You should check the fuel pressure in the line, and if it is low, inform the gas supply company |
A7 | Problems with the gas valve. Usually the cause is a control board failure | Diagnostics of the gas valve and its wiring. If necessary, replace the broken part with a new one |
A8 | There is a residual flame in the combustion chamber, although no voltage is supplied to the gas valve. The reason lies in a malfunction of the gas valve diaphragm | If the valve diaphragm is faulty, it must be replaced. If this does not help, you should change the control board |
A9 | Freezing - the coolant temperature has reached 5ºC | If the unit does not start automatically, you should turn it on |
AA | Boiling – the temperature of the liquid in the system has exceeded the permissible limit. This may have happened for the following reasons:
| The valves should be opened. Clean filters from debris. Check the functionality of the pump and three-way valve |
AND YOU | Thermostat malfunction. Perhaps the reasons are as follows:
| Diagnostics of thermostat contacts and the unit itself. Cleaning the contacts and connecting them to the thermostat. Replacing a faulty element |
AE | Smoke exhaust is difficult. It mainly occurs as a result of a clogged chimney or its deformation. | The chimney pipe needs to be cleaned |
Models of gas boilers Arderia B10, B14, B16 have different error codes. Let's look at what they mean and how to troubleshoot.
E0 – antifreeze mode. This code is displayed on the screen if the coolant temperature drops below +1°C. It is necessary to check the integrity of the system in which the liquid circulates. The error disappears if the coolant is heated. If it still hasn't disappeared, call a professional.
Code E1 indicates an ionization sensor error. This occurs when there is no expected flame. Appears as a result of unsuccessful ignition of the unit or after the flame fails during operation.
E2 – pressure sensor error. Appears as a result of weak draft, which is caused by malfunctions of the sensor or fan. The unit will attempt to return to normal operation for 15 minutes. Check the chimney and the presence of draft in it. If the error does not disappear after 15 minutes, contact the service center technician.
E3 – overheating thermostat error. Occurs when there is no coolant or its movement in the heating system. The circulation pump may be faulty. You should also check all valves and lines of the system. You can remove the lock using the MODE button. If this does not help, contact customer service.
E4 – overheating of temperature sensors. Appears on the screen due to the lack of fluid in the system or its circulation. Check the valves and heating pipe. The lock is released using the MODE button.
E5 – temperature sensor error. Appears when the cold water sensor is faulty. Turn off the hot water and wait. The lock can be released by pressing the MODE button. Code E6 – DHW sensor error. Appears when the DHW sensor is faulty. Close the hot water taps to normalize the heating system. The lock is released using the MODE button.
E7 – problem with the temperature sensor. Displayed when the heating circuit temperature sensor fails. Typically, this code appears when communication with the sensor is lost. When it gets better, the problem disappears.
E8 – indicates the presence of residual fire (ionization sensor error). Occurs if there is still fire in the combustion chamber or as a result of a sensor error. Unlock using the MODE button. If the error occurs again, contact customer service. E9 means pressure sensor error. Appears when fluid pressure is low or absent. You should check the system for leaks or adjust the speed at which the pump pumps coolant. It is necessary to eliminate any identified leaks or adjust the pump operation.
The fan starts working, but the flame does not appear
The air pressure switch does not work. Blocking the chimney. Leak in the combustion products exhaust system. The combustion chamber is not sealed. Power supply voltage is below 170 V. Install a voltage stabilizer
Incorrect combustion: flame color yellow or red
The burner is dirty. Incorrect functioning of the chimney. Incorrect gas valve setting.
Long waiting time for hot water
Since in the absence of water supply the water in the DHW pipe cools down, some time must pass before hot water appears from the tap.
The Arderia boiler often turns off: due to excessive temperature (error A4) or low pressure in the heating system (error A5).
Insufficient pressure, leaks or circulation problems in the heating system. It is necessary to check that the pressure in the heating system is within 1-1.2 bar, and that there are no leaks in the system. Checking the circulation in the heating system must be carried out by authorized personnel.
Presence of air in the heating system. Remove air.
Insufficient air pressure in the boiler expansion tank. Raise the air pressure in the tank to 1.0 bar - at zero pressure in the heating system.
The boiler pump shaft is blocked. The boiler pump is faulty. You need to call an authorized specialist.
Frequent spontaneous shutdowns of the boiler in DHW mode
Insufficient cold water pressure at the boiler inlet.
Ensure that the cold sanitary water inlet pressure is at least 1.5 bar. When using an individual water supply system with a hydraulic accumulator and uneven pressure, it is recommended that the pump turn on pressure be at least 2.0 bar.
Hot water flow too low. Do not set the water flow below 2 l/min, as this will trigger the DHW flow sensor and subsequently turn off the water heating. Random opening and closing of water taps respectively starts and stops the water heating process, which can lead to an increase in waiting time for hot water.
Fluctuations in hot water temperature
The simultaneous use of several hot water consumption points makes water consumption unstable. To reduce temperature fluctuations, do not use more than one hot water tap at a time.
The boiler burner does not turn on (error A6)
The power cord is not connected - connect the power cord. No gas supply - open the gas supply valve. The water temperature is set too low - set the temperature to a higher temperature using the regulator.
The appearance of strange sounds during boiler operation
There is air left in the pipes - bleed the air. Repeat filling the boiler with water. All shut-off valves are closed - open the shut-off valves. The Arderia boiler is not attached to the wall correctly - secure the boiler correctly. If the noise does not disappear, call a specialist from the service center.
The room does not warm up to a comfortable temperature
The boiler is operating in DHW mode - turn on the heating mode. The coolant temperature is set too low - set a higher temperature using the regulator. The shut-off valve in the heating circuit is closed - locate and open the valve. One or more taps in the heating circuit are not fully open - check all taps. Open partially closed ones. The boiler filter is clogged - clean the filter. There is air left in the pipes - bleed the air. Repeat filling the boiler with water.
No DHW
Clean the filter. The DHW stop tap is closed - open the DHW tap. The filter is clogged - clean the filter.
The boiler is overheating
Shut-off valves in the heating system are closed - check all valves. Open if they are closed.
Price range
The cost of Arderia gas boilers is significantly lower than that of similar devices made in Europe.
For a Russian buyer they cost 23-36 thousand rubles . The price of the unit depends on its power and additional functions. It must be taken into account that the chimney and remote control devices, room thermostat, etc. sold separately.
IMPORTANT!
You should not skimp on warranty service. The danger of being left without heating in winter is much more serious than the costs of concluding a warranty agreement.
Arderia gas boilers appeared on the Russian market relatively recently. Most users do not yet know about them, although a considerable number of units are already in operation.
They demonstrate stable operation, efficiency, and resistance to external loads . Self-diagnosis prevents boilers from malfunctioning; the built-in voltage stabilizer corrects fluctuations in the network. The quality and low cost of Arderia boilers allow them to take their rightful place among alternative options.
Instructions for Arderia boiler
Instructions for Arderia boiler
Gas boiler arderia b18 - heating boilers - buy by. Flushing the boiler arderia youtube. Error codes and malfunctions of gas boilers is known.
Typical problems with gas boilers | forumhouse.
How to connect a thermostat to a gas boiler! Detailed. Arderia gas boilers: operating instructions, how to. Cleaning the boiler. The water stopped heating. The village is steep. Problems with boilers | is your boiler faulty? You can not.
Design and installation of arderia and esr-2 boilers. 13 ffcd, esr.
How to clean and how to rinse a double-circuit heat exchanger.