Lemax boiler with turbo nozzle how to connect


Lemax gas floor-standing boiler with turbo nozzle in operation!

Best deals

Lemax gas floor-standing boiler with turbo nozzle in operation!

The Lemax turbo nozzle is designed for smoke removal from a gas boiler due to the built-in fan. The turbo nozzle itself is connected to the network and to the boiler automation; everything necessary for connection is included in the kit. Such a turbocharger can only be installed on a LEMAX gas floor-standing boiler with NOVA Sit 820 automation; an example of the designation of such a boiler is Lemax Premium 12.5 N (where N is the presence of NOVA Sit 820 automation). It is also possible to connect a room thermostat to such a boiler, which will allow you to regulate the room temperature more accurately. The thermostat itself can be removed from the boiler at a distance of up to 40 meters by connecting it with a wire to the automation.

mechanical room thermostat Cewal (Italy)

With the help of a turbo nozzle it is possible to avoid the construction of a natural draft chimney. This installation option will be convenient for those who want to get rid of a bulky chimney, or when designing a boiler room, immediately take into account its absence. The diameter of the outlet pipe from the turbo nozzle = 80 mm, the connecting diameter to the boiler is from 100 - 140 mm, depending on the power of the boiler.

— The turbocharger can be raised above the boiler to a height of no more than 500 m.

— The exiting pipe from the turbo nozzle should be inclined to the ground by 3-6 degrees. and at a distance from the ground of at least 2 meters.

— Minimum distance to doors, windows, open. horizontal ventilation grilles - 500 mm.

— The vertical distance from the windows located above the smoke duct opening is from 1 meter

- There should be no obstacles - walls, pillars, etc. - within 1.5 m from the pipe.

— Each turn of the pipe reduces its length by 500 mm. - 45 degrees, 1 meter - 90 degrees.

— To avoid clogging and blowing out, it is necessary to install a deflector on the chimney.

Installation diagram of a turbocharger on a Lemax gas boiler

How such a system looks in reality, watch the video:

gazboiler74.ru

Turbo nozzle for Lemax gas boiler

In today’s article we will try to tell you what a turbocharger for a Lemax gas boiler is, what boilers it is suitable for, and we will try to answer the question that was left on our forum on November 2 by user Igor.
The turbo nozzle is designed to remove combustion products in a forced manner, which allows the use of gas boilers without a specially organized natural draft chimney. For boilers with a power of 10 kW, the chimney diameter is 100 mm. For boilers with power from 12.5 to 30 kW. chimney diameter 130 mm. For boilers with power from 35 to 40 kW. chimney diameter 140 mm. The product has a fan installed at a rated voltage of 220 V. 50 Hz

The turbo nozzle consists of a housing on which a fan No. 3 with inlet and outlet pipes is installed. A pressure switch (air pressure switch) item 4 is installed on the housing, connected to the fan by a tube. All electrical connections are switched through the terminal block, item 7.

1 – Turbo nozzle base. 2 – Turbo nozzle cover. 3 – Fan 4 – Monostat. 5 – Monostat connection tube. 6 – Smoke exhaust pipe. 7 – Terminal block.

Device and operation. The turbo nozzle control unit is designed for connection to boilers equipped with safety automatics SIT 820 NOVA and SIT 845 Sigma .

The turbo nozzle performs forced removal of boiler combustion products based on a signal from the thermostat (the thermostat installed on the boiler maintains the temperature at the level specified by the consumer). In this case, the pressure switch (air pressure switch) closes the contacts only when the air pressure at the outlet of the turbo nozzle corresponds to the specified parameter. If the pressure in the chimney exceeds or falls below the set limit, the contacts will open and the boiler safety circuit will break. In the event of an emergency stop of the turbo fan or when the flue gas outlet is blocked, the operation of the boiler stops, that is, the safety automatic SIT 820 NOVA (volatile boiler control unit) stops the gas supply to the main burner.

Chimney pipe placement: ? if there is no condensate collector, it should be installed at an angle to the ground, preventing condensate from flowing back. The optimal slope is 3–6°. ? the minimum horizontal distance to doors, windows and open ventilation grilles (openings) should be 0.5 meters; ? the minimum distance to the top edge of doors, windows and open ventilation grilles (openings) should also be 0.5 meters; ? the vertical distance from the windows located above the smoke duct opening is from 1 meter; ? in the area of ​​1.5 meters from the pipe there should be no obstacles, say, walls, pillars, etc.; ? each turn reduces the length of the pipe by: 0.5 meters - 45 degrees, 1 meter - 90 degrees; ? To avoid clogging and blowing out, it is mandatory to install a deflector on the chimney

Diagram of a non-volatile boiler Group of contacts for automatic control 820 Nova

Connection diagram of the Lemax turbocharger to a boiler with SIT 820 Nova safety automatic and time delay unit (PML 1100 starter and PVL-22(21) attachment).

Connection diagram of the Lemax turbo nozzle to the boiler with a control board.

1. Disconnect wire No. 5 from connector No. 7. 2. Connect wire No. 5 to wire No. 3. 3. Disconnect wire No. 6 from connector No. 8. 4. Connect wire No. 6 to wire No. 4. 5. Connect wire No. 1 to connector No. 7. 6. Connect wire No. 2 to connector No. 8.

Source

Turbocharger Lemax L (d130, for boilers from 20 to 30 kW)

KaminDom is a trade organization that selects installation teams for the convenience of customers. The work is carried out by employees of our partners.

Call for a free consultation

Benefit for the buyer

1. Save time

Today it is important to receive a complete chain of services in one place. We have already spent time searching and checking teams for you.

2. Think about safety

Stoves, fireplaces and boilers are sources of extreme temperatures up to 750 °C. Special knowledge is required to install such equipment safely and avoid fire.

3. Making life more convenient

Installation by specialists is fast, safe and free from hassle. You won’t have to calculate the estimate yourself, go for missing materials, and there won’t be any left over.

4. We comply with warranty conditions

If you encounter any problems with the operation of your stove, boiler or fireplace, please contact the manufacturer. Most manufacturers guarantee the correct functioning of the product only when installed by professionals.

Installation stages

Departure of an engineer to measure
Calculation and approval of estimates
Delivery of goods and materials to the site
Installation and commissioning of the facility
Warranty service

Order an engineer visit

Advantages of our partners

1. Free of charge – engineer’s visit for measurements

When ordering, an inspection of the facility where the work will be carried out takes place. The cost of travel is 2000 rubles up to 50 km from the Moscow Ring Road, then it is negotiated individually in each case. But this amount is deducted from the total cost in the final calculation. If you want to speed up the process, save time and pay for installation services in full after signing the acceptance certificate, you can inspect the property online.

2. Wide range of works

Professional teams offer a different range of services: from chimney installation to decorative finishing of the fireplace. You don’t have to look for loaders, installers, or plasterers; our partners will complete the installation on a turnkey basis.

3. Flexible price

It is not necessary to order all possible services when, for example, you can properly organize thermal insulation yourself. Save money on this.

4. Reliability

Before installation, an agreement is concluded, without which no self-respecting team works. He confirms what and how will be done. After the services are completed, a transfer and acceptance certificate is signed. Please check your work carefully upon receipt!

5. 2 year warranty

The installation work carried out is guaranteed for 2 years. If during this time you discover defects caused by the actions of the installers, corrections are carried out at the expense of this team.

Order an engineer visit

DIY installation

First you need to know the requirements of fire safety rules SP 7.13130.2013. This is the main document in the Russian Federation used when installing boilers, stoves and fireplaces. Next, you need to understand the amount of materials needed, including fasteners, chimney elements, and even tiles with adhesive. You will also need knowledge of the physical and chemical properties of these materials in order to work and apply them correctly. Don't forget to take at least one assistant. It will be difficult for one person to install a stove and chimney; heating equipment weighs up to 400 kg, and the pipes themselves are only light at first glance. We will be glad if you master the intricacies of installing stoves, fireplaces, and boilers. Perhaps in the future you will become our partner.

Disclaimer

KaminDom is a trading organization; our employees do not perform installation. Only people who do this every day for several years will be experts in this matter. Therefore, we recommend our time-tested partners, carefully select them and do not cooperate with unscrupulous contractors. We are not responsible for the activities of installers, but we try to promptly help in resolving emerging issues. The installation teams are responsible for the quality, timing, cost and payment procedure. Please read the contract before concluding and do not sign the acceptance certificate without inspecting the work performed.

kamindom.ru

Installing a turbocharger on a Lemax boiler

Igor November 2, 2021 “I bought a LEMAX boiler of the PREMIUM series with SIT 820 NOVA automation and a LEMAX turbo nozzle. I invited him from the gas boiler service center to start the boiler and connect the turbo nozzle to the boiler. The nozzle was connected, but not quite correctly. The nozzle fan runs constantly. When the main gas burner is turned off, the fan does not stop. I drew the attention of specialists to this, and they repeatedly tried to correct this situation. But to no avail. In the end they left me. I have a question - how to connect the nozzle so that the fan stops when the main burner is turned off? Thank you in advance for your advice."

In today’s article we will try to tell you what a turbocharger for a Lemax gas boiler is, what boilers it is suitable for, and we will try to answer the question that was left on our forum on November 2 by user Igor.

The turbo nozzle is designed to remove combustion products in a forced manner, which allows the use of gas boilers without a specially organized natural draft chimney. For boilers with a power of 10 kW, the chimney diameter is 100 mm. For boilers with power from 12.5 to 30 kW. chimney diameter 130 mm. For boilers with power from 35 to 40 kW. chimney diameter 140 mm. The product has a fan installed at a rated voltage of 220 V. 50 Hz

The turbo nozzle consists of a housing on which a fan No. 3 with inlet and outlet pipes is installed. A pressure switch (air pressure switch) item 4 is installed on the housing, connected to the fan by a tube. All electrical connections are switched through the terminal block, item 7.

1 – Turbo nozzle base. 2 – Turbo nozzle cover. 3 – Fan 4 – Monostat. 5 – Monostat connection tube. 6 – Smoke exhaust pipe. 7 – Terminal block.

Device and operation. The turbo nozzle control unit is designed for connection to boilers equipped with safety automatics SIT 820 NOVA and SIT 845 Sigma .

The turbo nozzle performs forced removal of boiler combustion products based on a signal from the thermostat (the thermostat installed on the boiler maintains the temperature at the level specified by the consumer). In this case, the pressure switch (air pressure switch) closes the contacts only when the air pressure at the outlet of the turbo nozzle corresponds to the specified parameter. If the pressure in the chimney exceeds or falls below the set limit, the contacts will open and the boiler safety circuit will break. In the event of an emergency stop of the turbo fan or when the flue gas outlet is blocked, the operation of the boiler stops, that is, the safety automatic SIT 820 NOVA (volatile boiler control unit) stops the gas supply to the main burner.

Chimney pipe placement: ? if there is no condensate collector, it should be installed at an angle to the ground, preventing condensate from flowing back. The optimal slope is 3–6°. ? the minimum horizontal distance to doors, windows and open ventilation grilles (openings) should be 0.5 meters; ? the minimum distance to the top edge of doors, windows and open ventilation grilles (openings) should also be 0.5 meters; ? the vertical distance from the windows located above the smoke duct opening is from 1 meter; ? in the area of ​​1.5 meters from the pipe there should be no obstacles, say, walls, pillars, etc.; ? each turn reduces the length of the pipe by: 0.5 meters - 45 degrees, 1 meter - 90 degrees; ? To avoid clogging and blowing out, it is mandatory to install a deflector on the chimney

Diagram of a non-volatile boiler Group of contacts for automatic control 820 Nova

TP – safety thermostat TR – adjustable thermostat

Diagram of a Lemax turbocharger for a non-volatile boiler.

TP – safety thermostat TR – adjustable thermostat VT – fan PT – pressure switch (air pressure switch) RP – intermediate relay

Connection diagram of the Lemax turbocharger to a boiler with SIT 820 Nova safety automatic and time delay unit (PML 1100 starter and PVL-22(21) attachment).


TP – safety thermostat TR – adjustable thermostat BZV – Time delay unit

READ How to connect htc radar 110e to computer

Scheme of the Lemax turbocharger for a non-volatile boiler.

TP – safety thermostat TR – adjustable thermostat VT – fan PT – pressure switch (air pressure switch)

Connection diagram of the Lemax turbo nozzle to a boiler with automatic safety system SIT 820 Nova

TP – safety thermostat TR – adjustable thermostat

Connection diagram of the Lemax turbo nozzle to the boiler with a control board.


TR – thermal relay

Set of wires for connecting the Lemax turbo nozzle

P – pink B – white G – blue K – red F/G yellow-green

1. Disconnect wire No. 5 from connector No. 7. 2. Connect wire No. 5 to wire No. 3. 3. Disconnect wire No. 6 from connector No. 8. 4. Connect wire No. 6 to wire No. 4. 5. Connect wire No. 1 to connector No. 7. 6. Connect wire No. 2 to connector No. 8.

1. Security measures

1.1. The turbocharger must be installed and put into operation by the organization

tions that have permission for this type of work. To prepare the turbocharger for use, only specially trained personnel who have the appropriate electrical safety group, as well as knowledge of the regulatory operational documents of the facility where the product is installed, are allowed.

1.2. Work on transportation, installation and preparation of the turbocharger must be carried out in the absence of voltage in its electrical circuits.

2. Preparing the product for use

2.1. The turbocharger is installed on the boiler, and the smoke exhaust pipe is led outside; during installation it is necessary to ensure condensate drainage. (See Appendix A). When laying, the required fire resistance limits of their structures must be ensured in accordance with SNiP 41-01. During operation of the boiler, it is necessary to ensure that the air necessary for combustion enters the room.

2.2. The electrical connection of the turbo nozzle must be made in accordance with the diagram given in Appendix B.

2.3. When the boiler is operating, it is prohibited to place objects made of highly flammable materials closer than 200 mm (for example, wood fiber boards, polyurethane, polyethylene, lightweight PVC, synthetic fibers, cellulose substances, and the like).

2.4. After installation, check the correct operation of the turbo nozzle:

2.5. If the boiler does not have an overheating sensor installed (at 95 degrees/Celsius), it must be installed in the upper part of the heat exchanger and connected according to the “Turbo nozzle connection diagram” (see Appendix B).

1. The chimney from the boiler to the turbo nozzle must not create resistance to the movement of exhaust gases (constrictions or turns are not allowed).

2. The vacuum at the inlet to the turbo nozzle must be at least 5 Pa.

3. The turbo nozzle is designed to operate with a rated voltage of 220 V. 50 Hz.

4. The turbo nozzle is not intended for removing combustion products from solid fuel boilers, removing smoke during a fire, or for operating wall-mounted boilers.

5. When installing and servicing the turbo nozzle, electrical safety measures must be observed.

1. Maintenance must be performed at least once a year. Only specially trained personnel with an appropriate electrical safety group, as well as knowledge of the facility’s regulatory operational documents, are allowed to carry out maintenance. During maintenance, it is necessary to check the condition of the fan, monostat, and tubes, as well as electrical wires. Clean the turbo nozzle from dust and, if necessary, lubricate the moving parts with machine oil.

2. After completing the work, be sure to check the functionality of the turbo nozzle. (see clause 2.3.3.)

1 – Turbo nozzle base.

2 – Turbo nozzle cover.

5 – Monostat connection tube.

6 – Smoke exhaust pipe.

7 – Terminal block.

To ensure stable operation of TURB ONASAD KI, a deflector must be installed when installing the chimney.

TURBO UNIT DIAGRAM

TURBO UNIT CONNECTION DIAGRAM

The Lemax turbo nozzle is designed for smoke removal from a gas boiler due to the built-in fan. The turbo nozzle itself is connected to the network and to the boiler automation; everything necessary for connection is included in the kit. Such a turbocharger can only be installed on a LEMAX gas floor-standing boiler with NOVA Sit 820 automation; an example of the designation of such a boiler is Lemax Premium 12.5 N (where N is the presence of NOVA Sit 820 automation). It is also possible to connect a room thermostat to such a boiler, which will allow you to regulate the room temperature more accurately. The thermostat itself can be removed from the boiler at a distance of up to 40 meters by connecting it with a wire to the automation.

mechanical room thermostat Cewal (Italy)

With the help of a turbo nozzle it is possible to avoid the construction of a natural draft chimney. This installation option will be convenient for those who want to get rid of a bulky chimney, or when designing a boiler room, immediately take into account its absence. The diameter of the outlet pipe from the turbo nozzle = 80 mm, the connecting diameter to the boiler is from 100 – 140 mm, depending on the power of the boiler.

– The turbocharger can be raised above the boiler to a height of no more than 500 m.

– The exiting pipe from the turbo nozzle should be inclined towards the ground by 3-6 degrees. and at a distance from the ground of at least 2 meters.

– Minimum distance to doors, windows, open. horizontal ventilation grilles – 500 mm.

– The vertical distance from the windows located above the smoke duct opening is from 1 meter

– There should be no obstacles – walls, pillars, etc. – within 1.5 m from the pipe.

– Each turn of the pipe reduces its length by 500 mm. – 45 degrees, 1 meter – 90 degrees.

READ What is yota internet and how to connect it

– To avoid clogging and blowing, it is necessary to install a deflector on the chimney.

Installation diagram of a turbocharger on a Lemax gas boiler

How such a system looks in reality, watch the video:

Rating
( 1 rating, average 5 out of 5 )
Did you like the article? Share with friends: